蒸发器冷凝器选型计算
Use Up and Down arrows to view available values, Enter to select. Use Left and Right arrows to view selected values, Delete key to deselect.
| 套片式蒸发器换热参数计算 |
| 一、计算输入参数 |
| 压缩机型号 |
|
RB11H |
输入 |
|
|
| 制冷量KW |
Qo= |
40.00000 |
输入 |
|
|
| 压缩机输入功率KW |
Ni= |
12.19000 |
输入 |
|
|
| 压缩机排气量kg/h |
Gk= |
4471.00000 |
输入 |
|
|
| 冷凝温度℃ |
tk= |
50.00000 |
|
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
|
| 过热度℃ |
tr= |
5.00000 |
|
|
|
| 过冷度℃ |
tg= |
5.00000 |
|
|
|
| 蒸发器入口空气干球温度℃ |
ts1= |
27.00000 |
输入 |
|
|
| 蒸发器入口空气湿球温度℃ |
ts1s= |
19.50000 |
输入 |
|
|
| 蒸发器入口空气焓值kj/kg |
hs1= |
53.98430 |
输入 |
|
|
| 蒸发器出口空气干球温度℃ |
ts2= |
14.21000 |
输入 |
|
|
| 蒸发器出口空气湿球温度℃ |
ts2s= |
13.25000 |
输入 |
|
|
| 蒸发器出口空气焓值kj/kg |
hs2= |
37.48430 |
输入 |
|
|
| 冷凝温度℃ |
tk= |
50.00000 |
|
|
|
| 蒸发温度℃ |
to= |
7.00000 |
|
|
|
| 传热温差℃ |
△tm= |
10.99599 |
|
|
|
| 空气进出口风温差℃ |
△t= |
13.75000 |
|
|
|
| 进出口焓差kj/kg |
△h= |
16.50000 |
|
|
|
| 传热系数W/m2℃ |
K= |
45.00000 |
输入 |
|
|
| 最高冷凝温度℃ |
tkmax= |
60.00000 |
|
|
|
| 二、热力计算求解 |
| 蒸发器制冷量KW |
Qk= |
40.00000 |
|
|
|
| 蒸发器器传热面积m2 |
F= |
80.83752 |
|
|
|
| 冷凝风量m3/h |
Gk= |
8683.85346 |
|
|
|
| 三、蒸发器基本尺寸参数 |
| 换热器器水平管间距m |
A= |
0.02200 |
|
|
|
| 换热器垂直管间距m |
B= |
0.02540 |
|
|
|
| 换热管管径m |
D= |
0.01000 |
|
|
|
| 换热管内径m |
D1= |
0.00930 |
|
|
|
| 片距m |
d= |
0.00200 |
输入 |
|
|
| 单根换热管空气侧换热面积m2/m |
Fd= |
0.53572 |
|
|
|
| 单根换热管氟侧换热面积m2/m |
Fn= |
0.02920 |
|
|
|
| 单根换热管氟侧通流面积m2 |
Fds= |
0.00007 |
|
|
|
| 换热管肋化系数 |
τ= |
18.34515 |
|
|
|
| 二、换热器物理参数计算 |
| 蒸发器组数 |
N= |
1 |
输入 |
|
|
| 每组蒸发器表面管数 |
N1= |
58 |
输入 |
|
|
| 每组蒸发器排数 |
N2= |
4 |
输入 |
|
|
| 每组蒸发器管长m |
L= |
2.10 |
输入 |
|
|
| 每组冷凝器流程 |
N3= |
4 |
输入 |
|
|
| 每组分路数 |
n= |
58.00 |
计算值应为整数 |
|
|
| 每组蒸发器迎风面积m2 |
Fy= |
3.09372 |
|
|
|
| 每组蒸发器氟侧通流面积m2 |
Fsz= |
0.00394 |
|
|
|
| 每组蒸发换热面积m2 |
Fz= |
261.00035 |
必须满足校核值 |
|
|
| 蒸发器换热面积m2 |
F= |
261.00035 |
84.87939 |
根据选定排数输入计算风阻 |
| 热流密度W/m2 |
|
153.25650 |
450-500 |
空气阻力系数A |
| 冷风比m3/h:KW |
|
217.09634 |
130-220 |
2排 |
0.73 |
| 迎面风速m/s |
vy= |
0.77970 |
1.5-2.5 |
3排 |
0.85 |
| 空气侧阻力Pa |
△Pk= |
21.04005 |
≤180 |
4排 |
1 |
|
|
|
|
6排 |
1.12 |
|
|
|
|
|
| 干式蒸发器换热参数计算 |
|
| 一、计算输入参数 |
|
| 压缩机型号 |
|
SRS-S-163 |
输入 |
|
| 压缩机数量 |
|
1.00000 |
输入 |
|
| 制冷量KW |
Qo= |
137.20000 |
输入 |
|
| 压缩机输入功率KW |
Ni= |
45.60000 |
输入 |
|
| 压缩机标准工况下质量流量kg/h |
mf |
3268.00000 |
输入 |
|
| 压缩机排气量kg/h |
Gk= |
5881.00000 |
输入 |
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
| 过热度℃ |
tr= |
5.00000 |
|
|
| 过冷度℃ |
tg= |
5.00000 |
|
|
| 冷冻水进口温度℃ |
t1= |
12.00000 |
|
|
| 冷冻水出口温度℃ |
t2= |
7.00000 |
|
|
| 冷冻水出口温度范围℃ |
t2= |
5.0-15 |
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
| 传热温差℃ |
△tm= |
7.21348 |
|
|
| 冷冻水进出口温差℃ |
△t= |
5.00000 |
|
|
| 二、蒸发器热力计算求解 |
|
| 蒸发器制冷量KW |
Qk= |
137.20000 |
|
|
| 单位面积热负荷KW/m2 |
qf= |
9.00000 |
9.5-11 |
|
| 蒸发器传热面积m2 |
F= |
15.24444 |
|
|
| 冷冻水量kg/s |
Gk= |
0.00656 |
|
|
| 冷冻水量m3/h |
Gk= |
23.59866 |
|
|
| 三、蒸发器基本尺寸参数 |
|
| 换热器换热管间距m |
A= |
0.01700 |
|
|
| 排列方式 |
|
正三角形 |
|
|
| 换热管管径m |
D= |
0.01270 |
|
|
| 换热管内径m |
D1= |
0.01170 |
|
|
| 单根换热管每米管长换热面积m2/m |
Fd= |
0.03988 |
|
|
| 二、换热器物理参数计算 |
|
| 蒸发器组数 |
N= |
1 |
输入 |
|
| 每组蒸发器换热管数 |
N1= |
244 |
输入 |
|
| 每组蒸发器换热管长m |
L= |
1.9820 |
输入 |
|
| 每组蒸发器换热管流程 |
N3= |
4 |
输入 |
|
| 每组蒸发器每流程换热管数 |
N4= |
61 |
|
|
| 每组蒸发器水侧通流面积m2 |
Fy= |
|
|
|
| 每组蒸发换热面积m2 |
Fz= |
19.28532 |
必须满足校核值 |
|
| 蒸发器换热面积m2 |
F= |
19.28532 |
16.7689 |
1.1500655 |
| 冷却水流速m/s |
ω= |
|
1.0-1.4 |
|
| 摩擦阻力系数 |
f= |
|
|
|
| 水阻力KPa |
△Pk= |
|
100 |
|
|
|
|
|
|
| 水冷冷凝器换热参数计算 |
| 一、冷凝热计算输入参数 |
| 压缩机型号 |
|
SRS-S-252 |
输入 |
|
|
| 制冷量KW |
Qo= |
268.60000 |
输入 |
|
|
| 压缩机输入功率KW |
Ni= |
60.30000 |
输入 |
|
|
| 压缩机排气量kg/h |
Gk= |
5881.00000 |
输入 |
|
|
| 冷凝温度℃ |
tk= |
40.00000 |
|
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
|
| 过热度℃ |
tr= |
5.00000 |
|
|
|
| 过冷度℃ |
tg= |
5.00000 |
|
|
|
| 冷却水进口温度℃ |
t1= |
30.00000 |
|
|
|
| 冷却水出口温度℃ |
t2= |
35.00000 |
|
|
|
| 冷凝温度℃ |
tk= |
40.00000 |
|
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
|
| 传热温差℃ |
△tm= |
7.50000 |
|
|
|
| 冷却水进出口温差℃ |
△t= |
5.00000 |
|
|
|
| 冷却水进水温度范围℃ |
tk= |
16-33 |
|
|
|
| 二、冷凝器热力计算求解 |
| 冷凝器热负荷KW |
Qk= |
328.90000 |
|
|
|
| 单位面积热负荷KW/m2 |
qf= |
24.50000 |
22-27 |
|
|
| 冷凝器传热面积m2 |
F= |
13.42449 |
|
|
|
| 冷却水量kg/s |
Gk= |
0.01571 |
|
|
|
| 冷却水量m3/h |
Gk= |
56.57143 |
|
|
|
| 三、水冷冷凝器基本尺寸参数 |
| 换热器换热管间距m |
A= |
0.02000 |
|
|
|
| 排列方式 |
|
正三角形 |
|
|
|
| 换热管管径m |
D= |
0.01588 |
|
|
|
| 换热管内径m |
D1= |
0.01270 |
|
|
|
| 单根换热管氟侧换热面积m2/m |
Fd= |
0.04986 |
|
|
|
| 单根换热管水侧换热面积m2/m |
Fn= |
0.03988 |
|
|
|
| 单根换热管水侧通流面积m2 |
Fds= |
0.00013 |
|
|
|
| 二、换热器物理参数计算 |
| 冷凝器组数 |
N= |
1 |
输入 |
|
|
| 每组冷凝器换热管数 |
N1= |
150 |
输入 |
|
|
| 每组冷凝器换热管长m |
L= |
2.00 |
输入 |
|
|
| 每组冷凝器流程 |
N3= |
2 |
输入 |
|
|
| 每组冷凝器水侧通流面积m2 |
Fy= |
0.00950 |
|
|
|
| 每组冷凝换热面积m2 |
Fz= |
14.95896 |
必须满足校核值 |
|
|
| 冷凝器换热面积m2 |
F= |
14.95896 |
14.7669 |
|
| 冷却水流速m/s |
ω= |
1.65484 |
1.5-2.0 |
|
|
| 摩擦阻力系数 |
f= |
0.03977 |
|
|
|
| 水阻力KPa |
△Pk= |
23.31182 |
100 |
|
|
|
|
|
|
|
|
|
|
|
|
| 风冷冷凝器换热参数计算 |
| 一、冷凝热计算输入参数 |
| 压缩机型号 |
|
ZR19M3 |
输入 |
|
|
| 制冷量KW |
Qo= |
139.20000 |
输入 |
|
|
| 压缩机输入功率KW |
Ni= |
44.70000 |
输入 |
|
|
| 压缩机排气量kg/h |
Gk= |
|
输入 |
|
|
| 冷凝温度℃ |
tk= |
50.00000 |
|
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
|
| 过热度℃ |
tr= |
5.00000 |
|
|
|
| 过冷度℃ |
tg= |
5.00000 |
|
|
|
| 室外环境干球温度℃ |
tw= |
35.00000 |
|
|
|
| 室外环境湿球温度℃ |
tws= |
24.00000 |
|
|
|
| 冷凝温度℃ |
tk= |
50.00000 |
|
|
|
| 蒸发温度℃ |
to= |
2.00000 |
|
|
|
| 传热温差℃ |
△tm= |
9.82221 |
|
|
|
| 冷凝空气进风温度℃ |
t1= |
35.00000 |
输入 |
|
|
| 冷凝空气进风温度℃ |
t2= |
44.00000 |
输入 |
|
|
| 空气进出口风温差℃ |
△t= |
9.00000 |
|
|
|
| 传热系数W/m2℃ |
K= |
33.00000 |
输入 |
|
|
| 最高冷凝温度℃ |
tkmax= |
60.00000 |
|
|
|
| 二、冷凝器热力计算求解 |
| 冷凝器热负荷KW |
Qk= |
183.90000 |
|
|
|
| 风冷冷凝器传热面积m2 |
F= |
567.35982 |
|
|
|
| 冷凝风量kg/s |
Gk= |
20.33167 |
|
|
|
| 冷凝风量m3/h |
Gk= |
87832.83582 |
|
|
|
| 三、风冷冷凝器基本尺寸参数 |
| 换热器器水平管间距m |
A= |
0.02200 |
|
|
|
| 换热器垂直管间距m |
B= |
0.02540 |
|
|
|
| 换热管管径m |
D= |
0.01000 |
|
|
|
| 换热管内径m |
D1= |
0.00930 |
|
|
|
| 片距m |
d= |
0.00200 |
输入 |
|
|
| 单根换热管空气侧换热面积m2/m |
Fd= |
0.53572 |
|
|
|
| 单根换热管氟侧换热面积m2/m |
Fn= |
0.02920 |
|
|
|
| 单根换热管氟侧通流面积m2 |
Fds= |
0.00007 |
|
|
|
| 换热管肋化系数 |
τ= |
18.34515 |
|
|
|
| 二、换热器物理参数计算 |
| 冷凝器组数 |
N= |
4 |
输入 |
|
|
| 每组冷凝器表面管数 |
N1= |
42 |
输入 |
|
|
| 每组冷凝器排数 |
N2= |
3 |
输入 |
|
|
| 每组冷凝器管长m |
L= |
2.20 |
输入 |
|
|
| 每组冷凝器流程 |
N3= |
10 |
输入 |
|
|
| 每组分路数 |
n= |
12.60 |
计算值应为整数 |
|
|
| 每组冷凝器迎风面积m2 |
Fy= |
2.34696 |
|
|
|
| 每组冷凝器氟侧通流面积m2 |
Fsz= |
0.00086 |
|
|
|
| 每组冷凝换热面积m2 |
Fz= |
148.50020 |
必须满足校核值 |
|
|
| 冷凝器换热面积m2 |
F= |
594.00079 |
584.3806113 |
根据选定排数输入计算风阻 |
| 热流密度W/m2 |
|
309.59555 |
290-320 |
空气阻力系数A |
| 热风比m3/h:KW |
|
477.61194 |
≥320 |
2排 |
0.73 |
| 迎面风速m/s |
vy= |
2.59889 |
2.0-3.0 |
3排 |
0.85 |
| 空气侧阻力Pa |
△Pk= |
80.79957 |
|
4排 |
1 |
|
|
|
|
5排 |
1.12 |
|
|
|
|
|
| 146.6 |
173 |
200 |
13 |
20 |
26.5 |
40.5 |
52.6 |
63.5 |
79.5 |
99.5 |
125.5 |
| 29000 |
33100 |
37000 |
2800 |
4500 |
5600 |
8600 |
11500 |
14500 |
17500 |
21000 |
22500 |
| 15.155739 |
15.669648 |
16.20576 |
13.919591 |
13.324736 |
14.187275 |
14.118798 |
13.712892 |
13.12946 |
13.619784 |
14.205121 |
16.722544 |
|
|